Dgc-2020hd gestion du disjoncteur – Basler Electric DGC-2020HD Manuel d'utilisation

Page 115

Advertising
background image

9469370990 Rev B

105

Figure 45. Diagramme de flux des conditions de fermeture du disjoncteur des lignes principales

Mains Breaker

Close Request

Close Mains Breaker

Is

Mains Breaker

Control

enabled?

Mains Breaker

state

Cannot Close

Mains Breaker

No

Yes

Is Load

bus dead?

Is Mains bus

stable?

Perform sync check

P0071-73

Is Load

bus stable?

No

Is Load Bus

metered?

Generator

breaker state

Yes

Open

Cannot Close

Mains Breaker

Is

Generator Bus

stable?

Are buses

synchronized?

Yes

No

No

Yes

No

Yes

Live Bus Close

Enable Setting

Yes

Enabled

Close Mains Breaker

Closed

Open

Yes

No

Disabled

No

Generator

breaker state

Closed

Open

Closed

DGC-2020HD

Gestion du disjoncteur