Figure 43 – Basler Electric DGC-2020HD Manuel d'utilisation

Page 111

Advertising
background image

9469370990 Rev B

101

Figure 43. Diagramme de flux des conditions de fermeture du disjoncteur de l'alternateur

Generator Breaker

Close Request

Close Generator

Breaker

Is Generator

Breaker Control

enabled?

Generator

Breaker

state

Cannot Close

Generator Breaker

No

Yes

Is Load Bus

dead?

Is

Generator Bus

stable?

Synchronize buses

P0071-74

Is

Generator Bus

dead?

Dead Gen Close

Enable setting

No

No

Is Load

Bus stable?

No

Dead Bus Close

Enable setting

Disabled

No

Disabled

Enabled

Yes

Yes

Yes

Enabled

Yes

Open

Closed

DGC-2020HD