Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation

Page 97

Advertising
background image

Publication ICM-UM002F-EN-E - March 2013

97

I/O Data Tags

Apendix A

HighPassFilterSelection

SINT

Decimal

0 = 0.2 Hz
1 = 1 Hz
2 = 5 Hz
3 = 10 Hz (Default)
4 = 40 Hz

FrequencyMax

INT

Decimal

Default = 1000

LowPassFilterSelection

INT

Decimal

200 to 20,000 (Default = 1000)

TachometerRotations

INT

Decimal

1 to 65,535 (Default = 1)

RotorRotations

INT

Decimal

1 to 65,535 (Default = 1)

SpectrumLineCount

DINT

Decimal

100, 200, 400, 800 (Default = 200)

AveragesCount

INT

Decimal

1 to 99 (Default = 1)

SelectedSumHarmonicsOrder

SINT

Decimal

0=1
1=2
2=3
3=4
4=5
(Default = 3)

Band0OrderModeEn

BOOL

Decimal

0 = Hz (Default)
1 = Orders

Band1OrderModeEn

BOOL

Decimal

0 = Hz (Default)
1 = Orders

Band2OrderModeEn

BOOL

Decimal

0 = Hz (Default)
1 = Orders

Band3OrderModeEn

BOOL

Decimal

0 = Hz (Default)
1 = Orders

Band0MaxPeakEn

BOOL

Decimal

0 = Band Overall (Default)
1 = Maximum Peak

Band1MaxPeakEn

BOOL

Decimal

0 = Band Overall (Default)
1 = Maximum Peak

Band2MaxPeakEn

BOOL

Decimal

0 = Band Overall (Default)
1 = Maximum Peak

Band3MaxPeakEn

BOOL

Decimal

0 = Band Overall (Default)
1 = Maximum Peak

Band0FrequencyMin

INT

Decimal

Default = 1

Band0FrequencyMax

INT

Decimal

Default = 10

Band1FrequencyMin

INT

Decimal

Default = 1

Band1FrequencyMax

INT

Decimal

Default = 10

Band2FrequencyMin

INT

Decimal

Default = 1

Band2FrequencyMax

INT

Decimal

Default = 10

Band3FrequencyMin

INT

Decimal

Default = 1

Band3FrequencyMax

INT

Decimal

Default = 10

Module-defined Data Type: AB:1440_VDP_ChConfig_Struct:C:0

Member Name

Type

Default Display Style

Description

Advertising