42

Publication ICM-UM002F-EN-E - March 2013

Chapter 2 Installing the XM Dynamic Measurement Module

Connecting an IEPE Accelerometer and Non-Contact Sensor

The following figure shows the wiring of an IEPE accelerometer to channel 0
and the wiring of a non-contact sensor to channel 1.

Figure 2.22 IEPE Accelerometer and Non-Contact Sensor Wiring

ATTENTION

You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See

Terminal Block Assignments on page 28

.

IMPORTANT

Make certain the

Power parameter for each channel is set

correctly. Set channel 0

Power to IEPE and set channel 1

Power to -24V.

See Configure the Channel Properties on

page 64

for details.

TYPICAL WIRING FOR IEPE ACCELEROMETER AND NON-CONTACT

SENSOR TO XM DYNAMIC MEASUREMENT MODULE

Channel 0 Input Signal

Channel 1 Input Signal