Chapter 4 Troubleshoot the Module

Module Status (MS)

Indicator

The following table describes the module status indicator.

Network Status (NS)

Indicator

The following table describes the network status indicator.

Channel 0 and Channel 1

Status Indicators

The following table describes the channel indicators.

State

Probable Cause

Off

No power applied to the module.

Alternating Red/Green

Module performing power-up self-test.

Flashing Red

• Application firmware is invalid or not loaded.

Download firmware to the module.

• Firmware download is currently in progress.

Solid Red

An unrecoverable fault has occurred. The module may
need to be repaired or replaced.

Flashing Green

Module operating in Program Mode,

not performing its

monitoring functions.

Solid Green

Module operating in Run Mode, performing its monitoring
functions.

State

Probable Cause

Off

Module is not online.

• Module is autobauding.
• No power applied to the module; look at Module

Status LED.

Flashing Red

One or more I/O connections are in the timed-out state.

Solid Red

Failed communications (duplicate MAC ID or bus-off).

Flashing Green

Module is online but no connections are currently
established.

Solid Green

Module is online with connections currently established.

State

Probable Cause

Off

• Normal operation within alarm limits on the channel.
• No power applied to the module. Look at Module

Status LED.

Solid Yellow

An alarm associated with this channel is in Alert.

Solid Red

An alarm associated with this channel is in Danger.

Flashing Red

A transducer fault exists on the channel. The DC bias is
outside the DC Low and High Limits.

Advertising