Publication ICM-UM002F-EN-E - March 2013

133

CIP Objects

Appendix B

4

Get

Status

BOOL

Indicates if a fault or
alarm has occurred.

0 = Operating without alarms or
faults.
1 = Alarm or fault condition
exists. The

Overall Value

attribute may not represent the
actual field value.

5

Get

Data Units

ENGUNIT

The units context of the

Overall Value attribute.

This setting is determined by the
Channel Object’s

Output Data

Units attribute (see

page 128

).

6

Get/Set

Measurement

USINT

The measurement (or
calculation) performed to
produce the

Overall

Value.

0 = RMS
1 = RMS peak
2 = RMS pk-to-pk
3 = Peak
4 = Peak-to-peak
5-255 Reserved

7

Get

Time Constant

REAL

The detection time
constant associated with
the output smoothing
filter (for the RMS and DC
meters) or the decay rate
of the peak meters.

This setting is based on the

Low Frequency Cutoff
(Channel object) and

Measurement (attribute 6).
If

Measurement is set to 3 or

4, the Overall Time Constant is
1.5 seconds.
If

Measurement is set to 0, 1,

or 2, the table below shows the
Time Constant.

8

Get

Damping Factor

REAL

The damping factor
associated with output
smoothing filter for the
RMS and DC meters (not
used with peak meters).

1.0

9

Get/Set

Overall Filter

USINT

Overall filter type applied
to the input signal before
the measurement is
performed.

0 = None
1 = Low Pass Filter
2-255 Reserved

10

Get/Set

Low Pass
Corner
Frequency

UINT

The corner frequency of
the low pass filter.

200 to 20000 Hz

Table B.33 Overall Measurement Object Instance Attributes

Attr ID

Access

Rule

Name

Data Type

Description

Semantics

Low

Frequency

Cutoff

Overall

Time

Constant

0.2 Hz

0.8

1 Hz

0.16

5 Hz

0.045

10 Hz

0.045

40 Hz

0.045