Installing the XM Dynamic Measurement Module

Chapter 2

Connecting Two Accelerometers and a Non-Contact Sensor

The following figure shows the wiring of two IEPE accelerometers and a
non-contact sensor to the terminal base. The IEPE accelerometers are wired
to channel 0 and channel 1. The non-contact sensor is wired to the tachometer
input signal.

ATTENTION

You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See

Terminal Block Assignments on page 28

.

IMPORTANT

Make certain the

Power parameter is set to IEPE for both

channel 0 and channel 1 so power is provided to the
accelerometers.

See Configure the Channel Properties on

page 64

for details.

IMPORTANT

Transducer DC bias is monitored on all signals.