Publication ICM-UM002F-EN-E - March 2013

115

CIP Objects

Appendix B

Instance Attributes

Services

(1)

The AlarmLimitMultiply output tag in the RSLogix 5000 software can also set the Setpoint Multiplier switch. It
will not overwrite this service.

Table B.11 Discrete Input Object Instance Attributes

Attr ID

Access

Rule

Name

Data Type

Description

Semantics

3

Get

Value

BOOL

Alarm Limit Multiplier

0 = Off
1 = On

199

Set

Backdoor
Service

USINT

Setting this attribute is
equivalent to requesting
the specified service.

Set to one of the
following values to
perform the
specified service:
32

h

= Open

33

h

= Close

The virtual Setpoint
Multiplier switch
can be set with the
AlarmLimitMultiply
output tag in
RSLogix 5000
software.

Refer

to I/O Data Tags on
page 91.

Table B.12 Discrete Input Object Services

Service

Code

Class/Instance Usage

Name

Description

0E

h

Class/Instance

Get_Attribute_Single

Returns the contents of the
specified attribute.

10

h

Instance

Set_Attribute_Single

Sets the contents of the
specified attribute.

32

h

Instance

Open

Opens the virtual Setpoint
Multiplier switch

(1)

.

33

h

Instance

Close

Closes the virtual Setpoint
Multiplier switch

(1)

.