Identity object (class code 01h), Class attributes, Instance attributes – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation

Page 104: Class attributes instance attributes, Identity object (class code 01

Advertising
background image

104

Publication ICM-UM002F-EN-E - March 2013

Appendix B CIP Objects

Identity Object

(Class Code 01

H

)

The Identity Object provides identification and general information about the
device.

Class Attributes

The Identity Object provides no class attributes.

Instance Attributes

IMPORTANT

When the 1440-DYN02-RJ01 module is used with Logix
controllers, Logix automatically configures most of the CIP
objects using a Configuration Assembly. The Configuration
Assembly overwrites the values of some attributes that may be
set using the Services described in this appendix.

If you are using RSLogix 5000 software to configure the XM
module, we recommend you do not use the Services in this
appendix to configure signal processing, measurements, or
alarms because it will conflict with the RSLogix 5000
configuration.

Use the Services to collect data, for example Spectrum and
Time Waveforms. Since many measurements and diagnostic
information is reported to Logix in the input tag, you only need
to use these additional Services to collect data beyond what is
available in the input tag.

Refer to I/O Data Tags on page 91

for

more information about the input tag.

Identity Object Instance Attributes

Attr ID

Access

Name

Data Type

Default Value

1

Get

Vendor ID

UINT

1 = Allen-Bradley

2

Get

Device Type

UINT

109 (Specialty I/O)

3

Get

Product Code

UINT

21 (0x15) XM Dynamic Measurement
Module

4

Get Revision:

Major
Minor

STRUCT OF
USINT
USINT

Value varies with each firmware revision.
Value varies with each firmware revision.

5

Get

Status

WORD

6

Get

Serial Number

UDINT

7

Get Product

Name

SHORT_
STRING

XM Dynamic Measurement Module