Identity object (class code 01h), Class attributes, Instance attributes – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 104: Class attributes instance attributes, Identity object (class code 01
104
Publication ICM-UM002F-EN-E - March 2013
Appendix B CIP Objects
Identity Object
(Class Code 01
H
)
The Identity Object provides identification and general information about the
device.
Class Attributes
The Identity Object provides no class attributes.
Instance Attributes
IMPORTANT
When the 1440-DYN02-RJ01 module is used with Logix
controllers, Logix automatically configures most of the CIP
objects using a Configuration Assembly. The Configuration
Assembly overwrites the values of some attributes that may be
set using the Services described in this appendix.
If you are using RSLogix 5000 software to configure the XM
module, we recommend you do not use the Services in this
appendix to configure signal processing, measurements, or
alarms because it will conflict with the RSLogix 5000
configuration.
Use the Services to collect data, for example Spectrum and
Time Waveforms. Since many measurements and diagnostic
information is reported to Logix in the input tag, you only need
to use these additional Services to collect data beyond what is
available in the input tag.
Refer to I/O Data Tags on page 91
more information about the input tag.
Identity Object Instance Attributes
Attr ID
Access
Name
Data Type
Default Value
1
Get
Vendor ID
UINT
1 = Allen-Bradley
2
Get
Device Type
UINT
109 (Specialty I/O)
3
Get
Product Code
UINT
21 (0x15) XM Dynamic Measurement
Module
4
Get Revision:
Major
Minor
STRUCT OF
USINT
USINT
Value varies with each firmware revision.
Value varies with each firmware revision.
5
Get
Status
WORD
6
Get
Serial Number
UDINT
7
Get Product
Name
SHORT_
STRING
XM Dynamic Measurement Module