Publication ICM-UM002F-EN-E - March 2013

39

Installing the XM Dynamic Measurement Module

Chapter 2

Connecting a Powered Sensor

The following figures show the wiring of a powered sensor, such as the Model
580 Vibration Pickup, to the terminal base unit.

Figure 2.18 Powered Sensor to Channel 0 Wiring

ATTENTION

You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See

Terminal Block Assignments on page 28

.

IMPORTANT

Make certain the

Power parameter is set to +24V so power is

provided to the transducer.

See Configure the Channel

Properties on page 64

for details.

TYPICAL WIRING FOR MODEL 580 VIBR ATION PICKUP
TO XM DYNAMIC MEASUREMENT MODULE CHANNEL 0