Publication ICM-UM002F-EN-E - March 2013

93

I/O Data Tags

Apendix A

ModulePowerFault

BOOL

Faults:25

0 = No fault on 24V supply
1 = Fault on 24V supply; check the supply voltage to the module

CalibrationFault

BOOL

Faults:28

0 = No ROM fault
1 = ROM fault

AnyFault

BOOL

Faults:29

0 = No fault exists on the module
1 = At least one fault exists on the module

AnyFaultOrAlarm

BOOL

Faults:30

0 = No alarms or faults exist on the module
1 = At least one alarm or fault exists on the module

Status

DINT

Contains the following Status indicators

Ch0SpectrumStatus

BOOL

Status:8

0 = Band or vector data has been calculated
1 = Data has not been collected due to warm up period or speed limit
condition

Ch1SpectrumStatus

BOOL

Status:9

0 = Band or vector data has been calculated
1 = Data has not been collected due to warm up period or speed limit
condition

TachZeroPulseStatus

BOOL

Status:10

0 = No zero pulse tachometer fault
1 = Zero Pulse fault; tachometer is enabled and it is not receiving pulses

NetworkPowerStatus

BOOL

Status:11

0 = Power is applied at the external network terminal
1 = No power is detected at the external network terminal

AnyAlarmAlert

BOOL

Status:12

0 = No alarms are in Alert
1 = At least one alarm is in Alert

Ch0Alert

BOOL

Status:13

0 = No alarms on Channel 0
1 = Channel 0 has an alarm with a measurement in Alert

Ch1Alert

BOOL

Status:14

0 = No alarms on Channel 1
1 = Channel 1 has an alarm with a measurement in Alert

AnyAlarmDanger

BOOL

Status:15

0 = No alarms are in Danger
1 = At least one alarm is in Danger

Ch0Danger

BOOL

Status:16

0 = No alarms on Channel 0
1 = Channel 0 has an alarm with a measurement in Danger

Ch1Danger

BOOL

Status:17

0 = No alarms on Channel 1
1 = Channel 1 has an alarm with a measurement in Danger

RelaysHeld

BOOL

Status:18

Relay is being held at last state while in Idle mode

AlarmLimitMultiply

BOOL

Status:20

0 = Startup switch is not activated; alarm multiplier is not applied to the
alarm limits
1 = Startup switch is activated; alarm limit multiplier is applied to alarm
limits to avoid false alarms

StartupTime

BOOL

Status:21

0 = Currently not in startup time (alarm multiplier is not active)
1 = Currently in startup time (alarm multiplier is active) which means the
startup switch is activated or it is the start up period following the
release of the startup switch

Relay

BOOL

Status:23

0 = Relay 0 not tripped (conditions are not met)
1 = Relay 0 tripped

Alarms

DINT

Contains the following Alarm indicators

Module-defined Data Type: AB:1440_VDP_7FFFFFFF:I:0

(1)

Member Name

Type

Location

Description