Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 93
Publication ICM-UM002F-EN-E - March 2013
93
I/O Data Tags
Apendix A
ModulePowerFault
BOOL
Faults:25
0 = No fault on 24V supply
1 = Fault on 24V supply; check the supply voltage to the module
CalibrationFault
BOOL
Faults:28
0 = No ROM fault
1 = ROM fault
AnyFault
BOOL
Faults:29
0 = No fault exists on the module
1 = At least one fault exists on the module
AnyFaultOrAlarm
BOOL
Faults:30
0 = No alarms or faults exist on the module
1 = At least one alarm or fault exists on the module
Status
DINT
Contains the following Status indicators
Ch0SpectrumStatus
BOOL
Status:8
0 = Band or vector data has been calculated
1 = Data has not been collected due to warm up period or speed limit
condition
Ch1SpectrumStatus
BOOL
Status:9
0 = Band or vector data has been calculated
1 = Data has not been collected due to warm up period or speed limit
condition
TachZeroPulseStatus
BOOL
Status:10
0 = No zero pulse tachometer fault
1 = Zero Pulse fault; tachometer is enabled and it is not receiving pulses
NetworkPowerStatus
BOOL
Status:11
0 = Power is applied at the external network terminal
1 = No power is detected at the external network terminal
AnyAlarmAlert
BOOL
Status:12
0 = No alarms are in Alert
1 = At least one alarm is in Alert
Ch0Alert
BOOL
Status:13
0 = No alarms on Channel 0
1 = Channel 0 has an alarm with a measurement in Alert
Ch1Alert
BOOL
Status:14
0 = No alarms on Channel 1
1 = Channel 1 has an alarm with a measurement in Alert
AnyAlarmDanger
BOOL
Status:15
0 = No alarms are in Danger
1 = At least one alarm is in Danger
Ch0Danger
BOOL
Status:16
0 = No alarms on Channel 0
1 = Channel 0 has an alarm with a measurement in Danger
Ch1Danger
BOOL
Status:17
0 = No alarms on Channel 1
1 = Channel 1 has an alarm with a measurement in Danger
RelaysHeld
BOOL
Status:18
Relay is being held at last state while in Idle mode
AlarmLimitMultiply
BOOL
Status:20
0 = Startup switch is not activated; alarm multiplier is not applied to the
alarm limits
1 = Startup switch is activated; alarm limit multiplier is applied to alarm
limits to avoid false alarms
StartupTime
BOOL
Status:21
0 = Currently not in startup time (alarm multiplier is not active)
1 = Currently in startup time (alarm multiplier is active) which means the
startup switch is activated or it is the start up period following the
release of the startup switch
Relay
BOOL
Status:23
0 = Relay 0 not tripped (conditions are not met)
1 = Relay 0 tripped
Alarms
DINT
Contains the following Alarm indicators
Module-defined Data Type: AB:1440_VDP_7FFFFFFF:I:0
(1)
Member Name
Type
Location
Description