Installing the XM Dynamic Measurement Module

Chapter 2

The module is shipped from the factory with the node address set to 63 (as
shown below).

Follow the steps below to set the node address.

1.

Refer to XM Bus Node Address table on

page 52

for the switch settings

of a specific address.

2.

Using a pointed tool, slide switches 5 through 10 to the appropriate
positions (1 or 0).

DYNAMIC MEASUREMENT

1440-DYN02-01RJ

Switch 1...4 are not used

Switch 5...10 Node Address setting

TIP

The node addresses start with 1 for the module closest to the
ACNR, and increase for each consecutive module.

EXAMPLE

If you want the node address to be 4 then you would set dip
switches 5...8 as follows.

Up position = 1

Down position = 0