Chapter 2 Installing the XM Dynamic Measurement Module

XM Installation

Requirements

This section describes wire, power, grounding, and terminating resistor
requirements for an XM system that includes one 1440-ACNR ControlNet
Adapter module, and from one to ten 1440-DYN02-01RJ Dynamic
Measurement modules.

Wiring Requirements

Use solid or stranded wire. All wiring should meet the following specifications:

• 14 to 22 AWG copper conductors without pretreatment; 8 AWG

required for grounding the DIN rail for electromagnetic interference
(EMI) purposes

• Recommended strip length 8 millimeters (0.31 inches)

• Minimum insulation rating of 300V

• Soldering the conductor is forbidden

• Wire ferrules can be used with stranded conductors; copper ferrules

recommended

Power Requirements

Use a single Class 2 power supply to power the XM modules. Before installing
your module, calculate the power requirements of all modules in each chassis.
The total current draw through the side connector cannot exceed 3 A. Refer to
the specifications for the specific modules for power requirements.

Figure 2.1 is an illustration of wiring modules using separate power
connections.

IMPORTANT

The installation requirements may be different for different XM
modules. The following requirements apply only to the
1440-DYN02-01RJ module. Refer to the user manual for the
specific XM module for its requirements.