Publication ICM-UM002F-EN-E - March 2013

65

Configure XM Module in RSLogix 5000 Software

Chapter 3

1.

From the Module Properties dialog box, click the Channel tab.

2.

Click the Channel that you want to configure.

3.

Configure the parameters as necessary.

In this field

Values are

Comments

Channel Name

Enter a descriptive name for the channel.

The channel name is not sent to the XM
module.

Power

Choose the type of power supplied to the transducer.

• Off
• IEPE (externally supplied)
• -24V (externally supplied)
• +24V (externally supplied from the terminal base)
• Bias Current (externally supplied)

See Connecting the Transducer on page 34

for

wiring requirements.

See table below.

Approximate Expected Bias Voltage (V DC)

Power

Normal Connected Sensor

Open

Circuit

Short

Circuit

Unconnected

Sensor

DC Low

Limit Default

DC High Limit

Default

Off

sensor bias voltage (-10...10V DC typical)

2

0

2

-10

10

IEPE

sensor bias voltage (12...20V DC typical)

24

0

24

12

20

+24V

sensor bias voltage (1...20V DC typical)

2

0

2

1

20

-24V

sensor bias voltage (-14...-8V DC typical)

2

0

2

-14

-8

Bias Current

0.47V with 2000 ohm coil

13

0

13

0.2

2