Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation

Page 125

Advertising
background image

Publication ICM-UM002F-EN-E - March 2013

125

CIP Objects

Appendix B

10

Get/Set

AlarmLAlertLimit

REAL

The lesser threshold value
for the Alert state of the
alarm with a range
condition type.

11

Get/Set

AlarmLDangerLimit

REAL

The lesser threshold value
for the Danger state of
the alarm with a range
condition type.

12

Get/Set

AlarmDeadband

REAL

The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.

13

Get/Set

AlarmLimitMultiply
(Setpoint Multiplier)

REAL

Indicates how the
threshold should be
adjusted when the
setpoint multiplication
function is invoked.

0 = Disable alarm
> 0 = Multiply the thresholds by
the value

14

Get/Set

AlarmLimitMultiplyPeriod

UINT

The amount of time that
the Threshold (Setpoint)
Multiplier is applied after
the startup signal is
received.

Seconds

15

Get/Set

AlarmSpeedRangeEn

BOOL

Indicates whether this
alarm is enabled only
within a certain machine
speed range.

0 = No speed range (alarm is
always enabled)
1 = Speed range (alarm only
enabled within speed range)

16

Get/Set

AlarmSpeedHLimit

REAL

Indicates the greater
threshold of the machine
speed range for which the
alarm is enabled (disabled
at greater speeds).

CPM
(must be greater than

AlarmSpeedLLimit)

17

Get/Set

AlarmSpeedLLimit

REAL

Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).

CPM
(Must be less than

AlarmSpeedHLimit)

18

Get/Set

Name

STRING2

A name to help identify
this alarm.

19

Get/Set

Measurement Identifier

EPATH

Identifies the
measurement object to
which this alarm is
applied.

See Parameter Object instances
10 to 25. See

Table B.18 on

page 118

.

Table B.24 Alarm Object Instance Attributes

Attr ID

Access

Rule

Name

Data Type Description

Semantics