Chapter 2 Installing the XM Dynamic Measurement Module
Connecting a Non-contact Sensor
The following figures show the wiring of a non-contact sensor to the terminal
base unit.
Figure 2.14 Non-contact Sensor to Channel 0 Wiring
ATTENTION
You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See
Terminal Block Assignments on page 28
IMPORTANT
Make certain the
Power parameter is set to -24V to set the
buffered outputs to the appropriate range.
for details.