Chapter 2 Installing the XM Dynamic Measurement Module

Connecting a Non-contact Sensor

The following figures show the wiring of a non-contact sensor to the terminal
base unit.

Figure 2.14 Non-contact Sensor to Channel 0 Wiring

ATTENTION

You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See

Terminal Block Assignments on page 28

.

IMPORTANT

Make certain the

Power parameter is set to -24V to set the

buffered outputs to the appropriate range.

See Configure the

Channel Properties on page 64

for details.