Services – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation

Page 136

Advertising
background image

136

Publication ICM-UM002F-EN-E - March 2013

Appendix B CIP Objects

Services

(1)

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

12

Get/Set

Logic

USINT

Indicates the number of
associated alarms that
must have a status value
specified by

Alarm Level

in order to activate the
relay.

0 = Ignore

Alarm Identifier B

and activate the relay based on
the status of

Alarm Identifier

A.
1 = Activate the relay if the
status of either

Alarm

Identifier A or B matches any
of the statuses specified by

Alarm Level.
2 = Activate the relay if the
status of both

Alarm Identifier

A and B match any of the
statuses specified by

Alarm

Level.

14

Get

Relay Installed

BOOL

Indicates whether an
actual relay is associated
with this instance.

0 = Not installed
1 = Installed

15

Get/Set

Idle Hold

USINT

Hold relay state during
reconfiguration.

0 = Relay is deactivated while
module is in Program mode.
1 = Relay retains last state
while in Program mode.

Table B.36 Relay Object Instance Attributes

Attr ID

Access

Rule

Name

Data Type

Description

Semantics

Table B.37 Relay Object Services

Service

Code

Class/Instance Usage

Name

Description

05

h

Class/Instance

Reset

Resets latched relay.

0E

h

Class/Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Class/Instance

Set_Attribute_Single

Sets a single attribute.

(1)

Advertising