Installing the XM Dynamic Measurement Module

Chapter 2

Figure 2.15 Non-contact Sensor to Channel 1 Wiring

Connecting a Passive Transducer

The following figures show the wiring of a passive transducer, such as a
velocity sensor, to the terminal base unit.

TYPICAL WIRING FOR NON-CONTACT SENSOR

TO XM DYNAMIC MEASUREMENT MODULE CHANNEL 1

Channel 1 Input Signal

Signal Common

Shield

-24V DC

ATTENTION

You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See

Terminal Block Assignments on page 28

.

IMPORTANT

The module does not power the sensor. It measures only the
input voltage.

IMPORTANT

Make certain the

Power parameter is set to Bias Current.

See Configure the Channel Properties on page 64

for details.