Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation

Page 76

Advertising
background image

76

Publication ICM-UM002F-EN-E - March 2013

Chapter 3 Configure XM Module in RSLogix 5000 Software

1.

From the Module Properties dialog box, click the Band tab.

2.

Click the Channel that you want to configure.

3.

Configure the parameters, as necessary.

In this field

Values are

Comments

Channel Name

A descriptive name for the channel.

This can be entered on the Channel tab.

See

Configure the Channel Properties on page 64

.

Measurement Mode

Choose the measurement (or calculation) performed to
produce the Band Value.

• Band Overall - The band value is the square root of

the sum of the squares (RSS) of the amplitude
values for the bins that make up the band.

• Maximum Peak - The band value is equal to the

maximum bin amplitude found within the band.

Frequency Maximum

Enter the upper limit of the range of spectrum bins to
be included in the band measurement, and the
frequency units (Hz or Orders). Set the value using the
table below.

This value must be greater than the Band
Frequency Minimum.

Frequency Minimum

Enter the spectrum bin with the least frequency to be
included in the band measurement.

Sampling

Mode

Spectrum

Frequency

Max Units

Band Units

Band

Frequency

Max

Synchronous

Orders

Hz

0...5000

Orders

0.01...200

Asynchronous

Hz

Hz

0...20,000

Orders

0.01...200