Publication ICM-UM002F-EN-E - March 2013

Chapter 3 Configure XM Module in RSLogix 5000 Software

Configure the Module Definition Properties

The Module Definition dialog box allows you to modify module properties
and to select the measurements to be collected by the Dynamic Measurement
module. The measurements you select are used to calculate the size of the
connection and to generate the input tag data type.

1.

From the General tab, click Change.

2.

From the Module tab, enter the following information.

On this tab

In this field

Value/Comments

Module

Revision

Choose the appropriate major and/or minor revision of the module.

Electronic Keying

Choose the appropriate electronic keying method.

Connection

Data is the only valid choice.

Module Measurement Type

Standard Dynamic Measurement is the only valid measurement type.
This parameter determines the parameters and type of measurements
collected by the Dynamic Measurement module.

The Standard Dynamic Measurement Type supports measurements of
dynamic inputs such as vibration, pressure, and strain. It also provides a
tachometer that makes it particularly well-suited for monitoring shaft and
casing and pedestal vibration in rotating equipment.