Chapter 2 Installing the XM Dynamic Measurement Module

Figure 2.19 Powered Sensor to Channel 1 Wiring

Connecting a Process DC Voltage Signal

The following figures show the wiring from a process DC voltage signal to the
terminal base unit.

Channel 1 Input Signal

TYPICAL WIRING FOR MODEL 580 VIBRATION PICKUP

TO XM DYNAMIC MEASUREMENT MODULE CHANNEL 1

ATTENTION

You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See

Terminal Block Assignments on page 28

.

IMPORTANT

The module does not power the sensor. It measures only the
input voltage. Make certain the

Power parameter is set to

None.

See Configure the Channel Properties on page 64

for

details.