Chapter 3 Configure XM Module in RSLogix 5000 Software

4.

When finished, click one of these as needed.

• OK - Click to accept your edits and close the dialog box.
• Cancel - Click to close the dialog box without accepting your edits.
• Apply - Click to accept and apply your edits on any dialog box and

continue editing.

Configure the Tachometer Properties

The Tachometer tab defines the characteristics of the tachometer and the
signal processing that will be performed on the tachometer signal.

1.

From the Module Properties dialog box, click the Tachometer tab.

Enable Low Pass (Overall)
Filter

Check to apply a low pass filter to the Overall
Measurement.

Clear to disable the low pass filter.

The filter is applied only to the Overall
Measurement. It will not affect the time
waveform, spectrum, or measurements made
from the spectrum.

Low Pass Filter Corner

Enter the frequency value above which the input signal
will be significantly attenuated.

Enter a value between 200...20,000 Hz.

Note: This parameter is available only when
Enable Low Pass Filter is checked.

In this field

Values are

Comments