Publication ICM-UM002F-EN-E - March 2013

Chapter 2 Installing the XM Dynamic Measurement Module

1.

Make certain the keyswitch (D) on the terminal base unit (E) is at
position 1 as required for the module.

2.

Make certain the side connector (B) is pushed all the way to the left. You
cannot install the module unless the connector is fully extended

.

3.

Make sure that the pins on the bottom of the module are straight so they
will align properly with the connector in the terminal base unit.

4.

Position the module (A) with its alignment bar (G) aligned with the
groove (F) on the terminal base.

5.

Press firmly and evenly to seat the module in the terminal base unit. The
module is seated when the latching mechanism (C) is locked into the
module.

6.

Repeat the above steps to install the next module in its terminal base.

Basic Operations

Set the Node Address

The module has a DIP switch for setting the XM Bus node address. DIP
switches 5 through 10 set the module’s node address using binary addressing.

C

E

D

B

F

31886

G

A

DYNAMIC MEASUREMENT

1440-DYN02-01RJ