Publication ICM-UM002F-EN-E - March 2013

19

Installing the XM Dynamic Measurement Module

Chapter 2

Figure 2.1 XM Modules with Separate Power Connections

Grounding Requirements

Use these grounding requirements to ensure safe electrical operating
circumstances, and to help avoid potential EMI and ground noise that can
cause unfavorable operating conditions for your XM system.

31865

24 V

24 V COM

Supply

XM

®

XM

®

24 V COM

24 V

1

1

1

1

1

1

1

CAN HIGH

XM BUS COMMON

DRAIN WIRE

CAN LOW

Termination

resistor

121 ohm, 1%,

1/4W

Class 2

ATTENTION

To comply with the CE Low Voltage Directive (LVD), all
connections to this equipment must be powered from a source
compliant with the following: Safety Extra Low Voltage (SELV)
or Protected Extra Low Voltage (PELV).

To comply with UL restrictions, this equipment must be
powered from a source compliant with the following: Class 2.

ATTENTION

Multiple power sources are not allowed.

TIP

See Terminal Block Assignments on page 28

for the terminal

block assignments and descriptions for the Dynamic
Measurement module.