Publication ICM-UM002F-EN-E - March 2013

127

CIP Objects

Appendix B

Instance Attributes

Services

(1)

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

Table B.27 Band Measurement Object Instance Attributes

Attr ID

Access

Rule

Name

Data Type

Description

Semantics

3

Get

Band Value

REAL

The measured band value. See

Data Units

4

Get

Status

BOOL

Indicates if a fault or
alarm has occurred.

0 = Operating without alarms or
faults
1 = Alarm or fault condition
exists, the

Band Value

attribute may not represent the
actual field value.

5

Get

Data Units

ENGUNIT

The units context of the

Band Value attribute.

This attribute is read only. It is
set according to the

Output

Data Units attribute of the
associated Channel Object
instance. See

page 128

.

6

Get/Set

Measurement

USINT

The measurement (or
calculation) performed to
produce the

Band Value.

0 = RSS
1 = Peak

7

Get/Set

Minimum
Frequency

REAL

The minimum frequency
that is included in the
band measurement.

8

Get/Set

Maximum
Frequency

REAL

The maximum frequency
that is included in the
band measurement.

The Maximum Frequency must
be greater than or equal to

Minimum Frequency.

9

Get/Set

Frequency Units USINT

The units of

Minimum

and

Maximum

Frequency.

0 = Hz
1 = Orders

Table B.28 Band Measurement Object Services

Service

Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Instance

Set_Attribute_Single

Sets a single attribute.