Publication ICM-UM002F-EN-E - March 2013

79

Configure XM Module in RSLogix 5000 Software

Chapter 3

Measurement ID

Choose the measurement and channel that is
associated with the alarm.

• Ch 0 / Ch 1 Overall
• Ch 0 / Ch 1 DC Bias/Gap
• Ch 0 / Ch 1 Band 0
• Ch 0 / Ch 1 Band 1
• Ch 0 / Ch 1 Band 2
• Ch 0 / Ch 1 Band 3
• Speed
• SMAX Magnitude
• Ch 0 / Ch 1 1X Magnitude
• Ch 0 / Ch 1 2X Magnitude
• Ch 0 / Ch 1 3X Magnitude
• Ch 0 / Ch 1 Not 1X
• Ch 0 / Ch 1 Sum Harmonics
• Ch 0 / Ch 1 1X Phase
• Ch 0 / Ch 1 2X Phase
• SMAX Phase
• Acceleration

Multiple alarms can be set on the same
measurement.

Condition

Choose when the alarm should trigger.

• Greater Than - Trigger the alarm when the

measurement value is greater than or equal to the
Alert and Danger Limit values. The Danger High
Limit value must be greater than or equal to the
Alert High Limit value for the trigger to occur.

• Less Than - Trigger the alarm when the

measurement value is less than or equal to the
Alert and Danger Limit values. The Danger High
Limit value must be less than or equal to the Alert
High Limit value for the trigger to occur.

• Inside Range - Trigger the alarm when the

measurement value is equal to or inside the range
of the Alert and Danger Limit values. The Danger
High Limit value must be less than or equal to the
Alert High Limit value AND the Danger Low Limit
value must be greater than or equal to the Alert
Low Limit value for the trigger to occur.

• Outside Range - Trigger the alarm when the

measurement value is equal to or outside the range
of the Alert and Danger Limit values. The Danger
High Limit value must be greater than or equal to
the Alert High Limit value AND the Danger Low
Limit value must be less than or equal to the Alert
Low Limit value for the trigger to occur.

In this field

Values are

Comments