Publication ICM-UM002F-EN-E - March 2013

105

CIP Objects

Appendix B

Status

The Status is a 16 bit value. The following bits are implemented.

Identity Object Status

Bit

Name

Description

0

Owned

TRUE indicates that the module has an owner. More
specifically, the Predefined Master/Slave Connection Set
has been allocated to a master.

1

Reserved, set to 0

2

Configured

This bit is set whenever a saved configuration is
successfully loaded from non-volatile memory. This bit is
cleared whenever the default configuration is restored or
loaded.

3

Reserved, set to 0

4 - 7

Boot Program

Vendor-specific, indicates that the boot program is
running. The Main Application must be corrupt or
missing. Use ControlFlash to reload the Main
Application.

8

Minor Recoverable
Fault

Set whenever there is a transducer or tachometer fault.

9

Minor Unrecoverable
Fault

Not implemented

10 Major

Recoverable

Fault

Set when there is a major recoverable fault.

11

Major Unrecoverable
Fault

Set when there is a module status fault (Module Status
LED is solid red).

12 - 15

Reserved, set to 0

ID_STATUS_SELF_TESTING

0x0000

ID_STATUS_NVS_UPDATE 0x0010

ID_STATUS_COMM_FAULT

0x0020

ID_STATUS_AWAIT_CONN

0x0030

ID_STATUS_CONNECTED

0X0060

ID_STATUS_IDLE

0X0070