Tachometer status indicators, Setpoint multiplier indicator, Relay indicator – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation

Page 89

Advertising
background image

Publication ICM-UM002F-EN-E - March 2013

89

Troubleshoot the Module

Chapter 4

Tachometer Status

Indicators

The following table describes the tachometer indicator.

Setpoint Multiplier

Indicator

The following table describes the setpoint multiplier indicator

Relay Indicator

The following table describes the relay indicator.

Using RSLogix 5000

Software to Troubleshoot

Your Module

In addition to the status indicators on the module, RSLogix 5000 software
alerts you to fault conditions. You are alerted in one of these ways.

• Warning signal in the I/O Configuration next to the module when the

connection to the module is broken

• Fault message in a status line
• Notification in the Tag Monitor

General module

Diagnostic faults

• Status on the Connection and Module Info tabs

State

Probable Cause

Off

• Normal operation within alarm limits on the channel.
• No power applied to the module. Look at Module

Status LED.

Solid Yellow

An alarm on Speed or Acceleration is in Alert.

Solid Red

An alarm on Speed or Acceleration is in Danger.

Flashing Yellow

A tachometer fault other than a transducer fault (for
example, no pulse received).

Flashing Red

The tachometer signal DC bias is not within the DC Low
and High Limits.

State

Probable Cause

Off

The Alarm Limit Multiplier is not in effect.

Solid Yellow

The Alarm Limit Multiplier is in effect.

State

Probable Cause

Off

The virtual relay is not activated.

Solid Red

The virtual relay is activated.