background image

24

Publication ICM-UM002F-EN-E - March 2013

Chapter 2 Installing the XM Dynamic Measurement Module

Mounting the Terminal

Base Unit

The XM family includes several different terminal base units to serve all of the
XM modules. The 1440-TBS-J terminal base is the only terminal base used
with the Dynamic Measurement module (Cat. No. 1440-DYN02-01RJ).

The terminal base can be DIN rail or wall/panel mounted.

DIN Rail Mounting

Use the following steps to mount the terminal base unit on a DIN rail (A-B pt
no. 199-DR1 or 199-DR4).

1.

Position the terminal base on the 35 x 7.5 mm DIN rail (A).

WARNING

If you insert or remove the module while backplane power is on,
an electrical arc can occur. This could cause an explosion in
hazardous location installations.

Be sure that power is removed or the area is nonhazardous
before proceeding.

ATTENTION

Do not remove or replace a Terminal Base unit while power is
applied. Interruption of the backplane can result in
unintentional operation or machine motion.

31887-M

B

A

A

Position terminal base at a slight angle and hook over the top of the DIN rail.