Labconco Protecto Ech Filtered Fume Hoods 183 Series 8' Manuel d'utilisation

Page 151

Advertising
background image

Appendix E: gGuard

Product Service 1-800-522-7658

145

Original instructions

Option 1: “Static IP.” This is the most common option where the onsite IT provides Erlab

with the OP address, Subnet Mask, and Default Gateway.

At The Hood

Enter the provided IP, Subnet Mask, and GW.

Go to AdministrationNetwork ParametersEthernet

Set the DHCP “No” then enter the other information.

“Save and Exit.”

At the PC with gGuard

Open gGuardAdd/Delete a HoodAddIP

Now enter the IP address of the first hood thenconnect.

Option 2: “Dynamic IP.” This option is used when the DHCP and the IP address

automatically renews.

At the Hood

Go to AdministrationNetwork ParametersEthernet

Set the DHCP to “Yes.”

“Save and Exit.”

Now get the Mac# of the hood. To do this have the hood turned off but with power.

Remove the card that is in the card holder.

When the screen goes black press “Ok.”

The MAC will be displayed on the screen.

Example GifH0B0CE0024F8

Write it down.

At the PC with gGuard

Open gGuardAdd/Delete a HoodAddNetwork ID (MAC#).

Now enter the Mac address of the first hood thenconnect.

(The GifH must be entered exactly as it is case sensitive)

(Follow the instructions shown above)