Monitor data parameters – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 94

Advertising
background image

94

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 2

Configure the XM-124 Standard Dynamic Measurement Module

Monitor Data Parameters

Table 12 - Monitor Data Parameters

Parameter Name

Description

Values/Comments

States whether a transducer fault exists on the associated channel.
If a fault exists, the overall and gap values may not be accurate.

Possible status values:
No Fault
Fault

Shows the measured average DC offset of the transducer signal. This
value is compared with DC High Limit and DC Low Limit to determine
whether the transducer is working properly.

Overall

Shows the measured standard overall value.

gSE Overall

Shows the measured gSE Overall value.

Band Pass

Shows the measured Band Pass Filter value.

Tracked Mag

Shows the measured Tracking Filter Magnitude value.

Tracked Phase

Shows the measured Tracking Filter Phase value.

Eccentricity

Shows the measured Eccentricity value.

Thrust Position

Shows the measured Thrust Position value.

Shows the measured sum harmonics value.

The tachometer must be enabled (Pulses Per
Revolution
set to 1 or more), and a tachometer
signal must be present.

Band Measurement Status (XM Serial
Configuration Utility only)

States whether a fault condition exists on the associated channel. If a
fault exists, the band measurements may not be accurate.

Possible status values:
No Fault
Fault

Shows the measured band value.

Not 1X and Vector Status (XM Serial Configuration
Utility only)

States whether a fault condition exists on the associated channel. If a
fault exists, the not 1X and vector measurements may not be
accurate.
The following conditions can cause a fault:
Atransducer fault on the associated channel
No tachometer signal or a transducer fault exists on the

tachometer channel

The machine speed changes too fast for the tracking algorithm to

keep up or if the frequency of FMAX goes outside the specified
criteria (see Sampling Mode on

page 68

)

Possible status values:
No Fault
Fault

Not 1X Value

Shows the magnitude of the vibration excluding the vibration at the
machine speed.

The tachometer must be enabled (Pulses Per
Revolution
set to 1 or more), and a tachometer
signal must be present.

1X Magnitude

The magnitude of the vibration at the machine speed.

1X Phase

The phase of the vibration at the machine speed.

2X Magnitude

The magnitude of the vibration at two times the machine speed.

2X Phase

The phase of the vibration at two times the machine speed.

3X Magnitude

The magnitude of the vibration at three times the machine speed.

XM Configuration
Utility

EDS File

Transducer Fault

Transducer Status

XM Configuration
Utility

EDS File

DC Bias (Gap)

Measured DC Bias

XM Configuration
Utility

EDS File

Sum Harmonics

Sum Harmonics
Value

XM Configuration
Utility

EDS File

Band Measurement

Band Measured
Value