Install the XM-124 Standard Dynamic Measurement Module

Chapter 1

Mount the Module

The XM-124 standard dynamic measurement module (catalog number 1440-
SDM02-01RA) is used only with the 1440-TB-A/C terminal base.

1.

Make certain the keyswitch (D) on the terminal base unit (E) is at position
1 as required for the module.

2.

Make certain the side connector (B) is pushed all the way to the left. You
cannot install the module unless the connector is fully extended

.

3.

Make sure that the pins on the bottom of the module are straight so they
align properly with the connector in the terminal base unit.

4.

Position the module (A) with its alignment bar (G) aligned with the
groove (F) on the terminal base.

5.

Press firmly and evenly to seat the module in the terminal base unit. The
module is seated when the latching mechanism (C) is locked into the
module.

Repeat the above steps to install another module in its terminal base.

WARNING: If you insert or remove the module while backplane power
is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the
area is nonhazardous before proceeding.

WARNING: If you connect or disconnect wiring while the field-side
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the
area is nonhazardous before proceeding.

IMPORTANT

See XM Power Supply Solutions Application Technique, publication

ICM-AP005

,

for guidance in architecting power supplies for XM systems.