Instance attributes, Services, Instance attributes services – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 125

Advertising
background image

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

125

CIP Objects

Appendix B

Instance Attributes

Services

(1)

The AlarmLimitMultiply output tag in RSLogix 5000 software can also set the Setpoint Multiplier switch. It does not overwrite this
service.

Table 41 - Discrete Input Object Instance Attributes

Attr ID

Access Rule

Name Data

Type

Description

Semantics

3

Get

Value

BOOL

Alarm Limit Multiplier

0 = Off
1 = On

199

Set

Backdoor Service

USINT

Setting this attribute is equivalent
to requesting the specified service.

Set to one of the following
values to perform the
specified service:
32

h

= Open

33

h

= Close

The virtual Setpoint
Multiplier switch can be
set with the
AlarmLimitMultiply output
tag in RSLogix 5000
software.

Table 42 - Discrete Input Object Services

Service Code

Class/Instance Usage

Name

Description

0E

h

Class/Instance

Get_Attribute_Single Returns the contents of the specified

attribute.

10

h

Instance

Set_Attribute_Single

Sets the contents of the specified
attribute.

32

h

Instance

Open

Opens the virtual Setpoint Multiplier
switch

(1)

.

33

h

Instance

Close

Closes the virtual Setpoint Multiplier
switch

(1)

.

Advertising