Install the XM-124 Standard Dynamic Measurement Module

Chapter 1

Figure 30 - Typical Multiple XM Modules Remote Relay Reset Signal Connection

Connect the Setpoint Multiplication Switch

You can configure the module to multiply the alarm setpoints, or inhibit the
alarms during the start-up period. This can be used to avoid alarm conditions that
can occur during start-up, for example, when the monitored machine passes
through a critical speed.

Wire the Setpoint Multiplication switch to the terminal base unit as shown in

Figure 31

.

Figure 31 - Setpoint Multiplication Connection

Connect the 4…20 mA Outputs

The modules include an isolated 4…20 mA per channel output into a maximum
load of 300 ohms. The measurements that the 4…20 mA output tracks and the

ATTENTION: The Switch Input circuits are

functionally isolated from

other circuits. We recommend that the Switch RTN signal be grounded
at a signal point. Connect the Switch RTN signal to the XM terminal base
(chassis terminal) or directly to the DIN rail, or ground the signal at the
switch or other equipment that is wired to the switch.