Configure the XM-124 Standard Dynamic Measurement Module

Nominal Sensitivity

Choose the sensitivity of the transducer.

Your choice controls the list of possible full scale selections.

The default is 200.0 mV/mil (displacement).

Pressure 20.0 mV/ psi
50.0 mV/ psi
100.0 mV/ psi
0.29 mV/ mbar
0.73 mV/ mbar
1.45 mV/ mbar

Actual Sensitivity

Enter the sensitivity value of the transducer that is included with the
transducer’s calibration documentation. Due to manufacturing
variation, the actual sensitivity may be different than the nominal
sensitivity.

This value is ±15% of the

Nominal Sensitivity

value, see the

above table.

Important: The nominal sensitivity is used if you leave this
field blank.

DC High Limit

Enter the maximum expected DC bias voltage from the transducer.

Enter a value between -24…24V.

Important: A voltage reading outside this range constitutes
a transducer fault, which is indicated by the Channel status
indicator flashing red and the Ch0Fault or Ch1Fault input tag,
depending on the channel.

DC Low Limit

Enter the minimum, or most negative, expected DC voltage from the
transducer.

In this field

Values are

Comments

Quantity of
Measure

Nominal Sensitivity

Acceleration

10.0 mV/g
25.0 mV/g
50.0 mV/g
100.0 mV/g
500.0 mV/g
1000.0 mV/g
10000.0 mV/g

Velocity

100.0 mV/ in/s
150.0 mV/ in/s
200.0 mV/ in/s
400.0 mV/ in/s
500.0 mV/ in/s
1000.0 mV/ in/s
4.0 mV/ mm/s
6.0 mV/ mm/s
8.0 mV/ mm/s
16.0 mV/ mm/s
20.0 mV/ mm/s
40.0 mV/ mm/s

Displacement

100.0 mV/ mil
150.0 mV/ mil
200.0 mV/ mil
285.0 mV/ mil
10.0 mV/ mil
3.94 mV/ μm
5.91 mV/ μm
7.87 mV/ μm
11.2 mV/ μm
0.394 mV/μm

Pressure

20.0 mV/ psi
50.0 mV/ psi
100.0 mV/ psi
0.29 mV/ mbar
0.73 mV/ mbar
1.45 mV/ mbar

Volts

1000.0 mV/V