Connect the remote relay reset signal – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 46

Advertising
background image

46

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 1

Install the XM-124 Standard Dynamic Measurement Module

Connect the Remote Relay Reset Signal

If you set the module relay to latching and the relay activates, the relay stays
activated even when the condition that caused the alarm has ended. The remote
relay reset signal enables you to reset your module relay remotely after you have
corrected the alarm condition. This includes latched relays in the Expansion
Relay module when it is attached to the XM-124 module.

Wire the Remote Relay Reset Signal to the terminal base unit as shown in

Figure 29

.

Figure 29 - Remote Relay Reset Signal Connection

A single switch contact can also be shared by multiple XM modules wired in
parallel as shown in

Figure 30

.

TIP

If you set a module relay to latching, make sure that any linked relays, such
as relays in an XM-440 Master Relay Module, are not configured as
latching. When both relays are set to latching, the relay in each module has
to be independently reset when necessary.

TIP

You can discretely reset a relay using the serial or remote configuration tool.

ATTENTION: The Switch Input circuits are

functionally isolated from

other circuits. We recommend that the Switch RTN signal be grounded
at a signal point. Connect the Switch RTN signal to the XM terminal base
(chassis terminal) or directly to the DIN rail, or ground the signal at the
switch or other equipment that is wired to the switch.

ATTENTION: The relay reset connections may be different for different
XM modules.

Figure 30

applies only to the XM-124 module. Refer to the

installation instructions for the module for its terminal assignments.