Module status (ms) indicators, Relay indicator, Network status (ns) indicator – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 112: Channel 1 and channel 2 status indicators

Advertising
background image

112

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Appendix A

Status Indicators

Module Status (MS)
Indicators

The following table describes the Module Status indicators.

Relay Indicator

The following table describes the relay indicator.

Network Status (NS)
Indicator

The following table describes the network status indicator.

Channel 1 and Channel 2
Status Indicators

The following table describes the channel indicators.

State

Probable Cause

Off

No power applied to the module.

Alternating Red/Green

Module performing power-up self-test.

Flashing Red

Application firmware is invalid or not loaded. Download firmware to the

module.

Firmware download is currently in progress.
The Node Address or Communication Rate DIP switches have been

changed and do not reflect the settings currently in use.

Solid Red

An unrecoverable fault has occurred. The module may need to be repaired or
replaced.

Flashing Green

Module operating in Program Mode,

not performing its monitoring

functions.

Solid Green

Module operating in Run Mode, performing its monitoring functions.

State

Probable Cause

Off

The relay is not activated.

Solid Red

The relay is activated.

State

Probable Cause

Off

Module is not online.
Module is autobauding.
No power applied to the module; look at Module Status indicator.

Flashing Red

One or more I/O connections are in the timed-out state.

Solid Red

Failed communication (duplicate MAC ID or bus-off).

Flashing Green

Module is online but no connections are currently established.

Solid Green

Module is online with connections currently established.

State

Probable Cause

Off

Normal operation within alarm limits on the channel.
No power applied to the module. Look at Module Status indicator.

Solid Yellow

An alarm associated with this channel is in Alert.

Solid Red

An alarm associated with this channel is in Danger.

Flashing Red

A transducer fault exists on the channel. The DC bias is outside the DC Low
and High Limits.

Advertising