Cos message format, Xm status values – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 104

Advertising
background image

104

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 3

Operate the Module

COS Message Format

The XM-124 module’s COS message contains 8 bytes of data as defined in the
table below. The COS data can also be requested explicitly through Assembly
Object (Class ID 0x4), Instance 100 (0x64), Data Attribute (3).

XM Status Values

The following tables describe the XM Status values that are included in the COS
messages.

Table 17 - XM-124 COS Message Format

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Relay 1 Status

Setpoint Multiplier
Status

Alarm 2 Status

Alarm 1 Status

1

Relay 2 Status

Channel 1 Transducer
Status

Alarm 4 Status

Alarm 3 Status

2

Relay 3 Status

Channel 2 Transducer
Status

Alarm 6 Status

Alarm 5 Status

3

Relay 4 Status

Tachometer
Transducer Status

Alarm 8 Status

Alarm 7 Status

4

Relay 5 Status

Reserved

Alarm 10 Status

Alarm 9 Status

5

Reserved

Reserved

Alarm 12 Status

Alarm 11 Status

6

Reserved

Reserved

Alarm 14 Status

Alarm 13 Status

7

Reserved

Reserved

Alarm 16 Status

Alarm 15 Status

Table 18 - Alarm Status Descriptions

Alarm Status Value

Description

0

Normal

1

Alert

2

Danger

3

Disarm

4

Transducer Fault (Sensor OOR)

5

Module Fault

6

Tachometer Fault

7

Reserved

Table 19 - Setpoint Multiplier Status Descriptions

Setpoint Multiplier Status Value

Description

0

Not Activated

1

Activated

Advertising