Connect a passive transducer – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 37

Advertising
background image

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

37

Install the XM-124 Standard Dynamic Measurement Module

Chapter 1

Figure 19 - Non-contact Sensor to Channel 2 Wiring

Connect a Passive Transducer

The figures below show the wiring of a passive transducer, such as a velocity
sensor, to the terminal base unit.

TYPICAL WIRING FOR NON- CONTACT SENSOR

TO XM-120/121 DYNAMI C MEASUREMENT MODULE C HANNEL 2

COM

SIG

-24

Channel 2 Input Signal

-24V DC

1

17

22

Signal Common

21

Jumper ing terminal 21 to
terminal 22 configures
CH 2 buffer for -24V to +9V

Isolated Sensor Driver

Shield

Shield
Fl oating

38

TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 2

ATTENTION: You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the transducer.
Any convenient chassis terminal may be used (see

Terminal Block

Assignments

on page 27).

IMPORTANT

The module does not power the sensor. It measures only the input voltage.