Chapter 2

Configure the XM-124 Standard Dynamic Measurement Module

Alarm, Relay, and 4…20 mA Output Parameters

Use this dialog box to configure alarms, relays, and the analog output signal. The
4…20 mA output has no dependencies, so these may be configured in any order.
However, the relay logic is dependent on alarms, so always configure alarms
before relays.

Table 7 - Alarm Parameters

Parameter Name

Description

Values/Comments

Number (1…16) (XM Serial Configuration Utility
only)

Sets the alarm to be configured in the XM Serial Configuration Utility.
There are 16 alarms in the XM-124 module. The alarms are not
restricted to a channel.

Select a number from 1…16.

Name (XM Serial Configuration Utility only)

A descriptive name to identify the alarm in the XM Serial
Configuration Utility.

Maximum 18 characters

Enable

Enable/disable the selected alarm.
Important: The Alarm Status is set to ‘Disarm’ when the alarm is
disabled.

Measurement

The type of measurement and the channel that is associated with the
alarm.
Important: A maximum of eight alarms can be associated with any
one measurement.

Options: Ch1 / Ch2 Overall
Ch1 / Ch2 Gap
Ch1 / Ch2 Band 1–4
Speed
Mag
Ch1 / Ch2 1X Mag
Ch1 / Ch2 2X Mag
Ch1 / Ch2 3X Mag
Ch1 / Ch2 Not 1X
Ch1 / Ch2 Sum Harmonics
Ch1 / Ch2 1X Phase
Ch1 / Ch2 2X Phase
Phase
Acceleration
Ch1 / Ch2 Thrust Position
Ch1 / Ch2 gSE Overall
Ch1 / Ch2 Tracking Mag
Ch1 / Ch2 Tracking Phase
Ch1 / Ch2 Band Pass
Ch1 / Ch2 Eccentricity

Condition

Controls when the alarm triggers:
• Greater than - Triggers the alarm when the measurement value

is greater than or equal to the Alert and Danger Threshold
values.

The Danger Threshold value must be greater than or equal to the

Alert Threshold value for the trigger to occur.

• Less than - Triggers the alarm when the measurement value is

less than or equal to the Alert and Danger Threshold values.

The Danger Threshold value must be less than or equal to the Alert

Threshold value for the trigger to occur.

• Inside range - Triggers the alarm when the measurement value

is equal to or inside the range of the Alert and Danger
Threshold
values.

The Danger Threshold (High) value must be less than or equal to

the Alert Threshold (High) value AND the Danger Threshold (Low)
value must be greater than or equal to the Alert Threshold (Low)
value for the trigger to occur.

• Outside range - Triggers the alarm when the measurement value

is equal to or outside the range of the Alert and Danger
Threshold
values.

The Danger Threshold (High) value must be greater than or equal

to the Alert Threshold (High) value, AND the Danger Threshold
(Low) value must be less than or equal to the Alert Threshold
(Low) value for the trigger to occur.

Options:
Greater Than
Less Than
Inside Range
Outside Range
Important: This parameter is not applicable for a
vector (phase) alarm type or phase measurement.

XM Configuration
Utility

EDS File

Check to Enable

Enabled

Clear to Disable

Disabled