Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 84

Advertising
background image

84

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 2

Configure the XM-124 Standard Dynamic Measurement Module

Sets the relay activation logic:
• A or B - Relay is activated when either Alarm A or Alarm B meets

or exceeds the selected Alarm Status condition.

• A and B - Relay is activated when both Alarm A and Alarm B

meet or exceed the selected Alarm Status condition.

• A Only - Relay is activated when Alarm A meets or exceeds the

selected Alarm Status condition.

Options:
A only
A or B
A and B

Sets the alarm that the relay monitors. The alarm must be from the
same device as the relay. When the Activation Logic is set to ‘A and
B’ or ‘A or B’ you can select an alarm in both Alarm A and Alarm B.
The system monitors both alarms. When the Activation Logic is set
to ‘A Only,’ you can select an alarm only in Alarm A.

Alarm No. 1…16
Important: You can only select an alarm that is
enabled.

Sets the alarm conditions that cause the relay to activate. You can
select more than one:
• Normal - The current measurement is not within excess of any

alarm thresholds.

Alert - The current measurement is in excess of the alert level

threshold but not in excess of the danger level threshold.

• Danger - The current measurement is in excess of the danger level

threshold.

• Disarm-The alarm is disabled or the device is in Program mode.
• Xdcr Fault - A transducer fault is detected on the associated

transducer.

• Module Fault - Hardware or firmware failure, or an error has

been detected and is preventing proper operation of the device.

• Tacho Fault - A required tachometer signal has not been

detected. Note that there is no transducer fault either.

Options:
Normal
Danger
Xdcr Fault
Tacho Fault
Alert
Disarm
Module Fault

Check to enable.
Clear to disable.

Relay Installed

Indicates whether the relay is a physical relay on a module or a virtual
relay. If the relay is a physical relay, then you can set the Failsafe
parameter.
If the relay is a virtual relay, the Failsafe parameter is not used or it is
disabled.

Determines whether the relay is failsafe or non-failsafe.
Failsafe operation means that when in alarm, the relay contacts are in
their ‘normal’, de-energized, or ‘shelf-state’ positions. In other words,
normally closed relays are closed in alarm, and normally open relays
are open in alarm. With failsafe operation, a power failure equals an
alarm.
The following are true of a relay in failsafe operation:
The relay is energized when power is applied to the module.
The relay in a nonalarmed condition has power applied to the coil.
In alarm condition, power is removed from the relay coil, causing

the relay to change state.

For non-failsafe operation, the following are true:
Under nonalarm conditions, the relay closes the circuit between

the common and the N.C. (normally closed) terminals.

Under alarm conditions, the relay changes state to close the circuit

between the common and the N.O. (normally open) terminals.

For failsafe operation, the following are true:
Under nonalarm (with power applied to the unit) conditions, the

relay closes the circuit between the common and the N.O.
terminals.

Under alarm or loss-of-power conditions, the relay changes state

to close the circuit between the common and the N.C. terminals.

Table 8 - Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Activation Logic

Logic

XM Configuration
Utility

EDS File

Alarm A/B

Alarm Identifier
A/B

XM Configuration
Utility

EDS File

Alarm Status to Activate
On

Alarm Levels

XM Configuration
Utility

EDS File

Check = Physical Relay

Installed = Physical
Relay

Clear = Virtual Relay

Not Installed =
Virtual Relay

XM Configuration
Utility

EDS File

Failsafe Relay

Failsafe Option

XM Configuration
Utility

EDS File

Check means failsafe

Failsafe

Clear means non-failsafe

Nonfailsafe

Advertising