Instance 101 - measurement values – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 120

Advertising
background image

120

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Appendix B

CIP Objects

Instance 101 - Measurement Values

This assembly instance can be selected to be sent in response to an I/O Poll
Request from a Master. This instance is the default Poll response selection for
firmware version 3 or later, and it is the only available Poll response for firmware
versions 1 and 2.

Table 34 - Instance 101 Data Format (measurement values assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0…3

Channel 1 Overall value

4…7

Channel 2 Overall value

8…11

Channel 1 Gap value (Analog Input Point (AIP) Object Instance #1)

12…15

Channel 2 Gap value (AIP Object Instance #2)

16…19

Speed value

20…23

Maximum Speed value

24…27

Channel 1 Band 1 value

28…31

Channel 2 Band 1 value

32…35

Channel 1 Band 2 value

36…39

Channel 2 Band 2 value

40…43

Channel 1 Band 3 value

44…47

Channel 2 Band 3 value

48…51

Channel 1 Band 4 value

52…55

Channel 2 Band 4 value

56…59

Channel 1 Vector 1 Magnitude value

60…63

Channel 1 Vector 1 Phase value

64…67

Channel 2 Vector 1 Magnitude value

68…71

Channel 2 Vector 1 Phase value

72…75

Channel 1 Vector 2 Magnitude value

76…79

Channel 1 Vector 2 Phase value

80…83

Channel 2 Vector 2 Magnitude value

84…87

Channel 2 Vector 2 Phase value

88…91

Channel 1 Vector 3 Magnitude value

92…95

Channel 2 Vector 3 Magnitude value

96…99

Channel 1 Not 1X value (AIP Object Instance #3)

100…103

Channel 2 Not 1X value (AIP Object Instance #4)

104…107

SMAX Magnitude value (AIP Object Instance #5)

108…111

SMAX Phase value (AIP Object Instance #6)

112…115

Channel 1 Sum Harmonics value (AIP Object Instance #7)

116…119

Channel 2 Sum Harmonics (AIP Object Instance #8)

120…123

Channel 1 Position measurement

124…127

Channel 2 Position measurement

128…131

Acceleration measurement value

132

Channel 1 Measurement Mode

Advertising