Instance attributes, Status, Identity object status t – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 116: Instance attributes status

Advertising
background image

116

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Appendix B

CIP Objects

Instance Attributes

Status

The Status is a 16 bit value. The following bits are implemented.

Table 24 - Identity Object Instance Attributes

Attr ID

Access

Name

Data Type

Default Value

1

Get

Vendor ID

UINT

1 = Allen-Bradley

2

Get

Device Type

UINT

109 (Specialty I/O)

3

Get

Product Code

UINT

73

4

Get Revision:

Major
Minor

STRUCT OF USINT
USINT

Value varies with each firmware version.
Value varies with each firmware version.

5

Get

Status

WORD

6

Get

Serial Number

UDINT

7

Get Product

Name

SHORT_
STRING

XM-124 standard dynamic measurement module

Table 25 - Identity Object Status

Bit

Name

Description

0

Owned

TRUE indicates that the module has an owner. More specifically, the Predefined Master/Slave Connection Set has
been allocated to a master.

1

Reserved, set to 0

2

Configured

This bit is set whenever a saved configuration is successfully loaded from nonvolatile memory. This bit is cleared
whenever the default configuration is restored or loaded.

3

Reserved, set to 0

4 …7

Extended Device Status

8

Minor Recoverable Fault

Set whenever there is a transducer or tachometer fault.

9

Minor Unrecoverable Fault

Not implemented

Self-testing or unknown

0

Firmware update in progress

1

At least one faulted I/O connection

2

No I/O connections established

3

At least one I/O connection in Run mode

6

At least one I/O connection, all in Run mode

7