Transducer Object
(Class ID 328

H

)

The Transducer Object models a transducer.

Class Attributes

The Transducer Object provides no class attributes.

Instances

There are three instances of this object.

Instance Attributes

Table 79 - Band Measurement Object Instances

Instance

Descriptions

1

Vibration Channel 0

2

Vibration Channel 1

3

Tachometer Channel

Table 80 - Transducer Object Instance Attributes

Attr ID

Access Rule

Name Data

Type

Description

Semantics

3

Get

DC Bias

REAL

The measured average DC bias of
the transducer signal in volts.

Volts

4

Get

Status

BOOL

Indicates whether a transducer
fault exists (the measured DC Bias
is outside the range specified by
Fault High and Low).

0 = No fault
1 = A transducer fault exists

5

Get/Set

Sensitivity Value

REAL

Value of the sensitivity of the
transducer in millivolts per
Sensitivity Units.

See Valid Full Scale Selections for valid
Sensitivity and Full Scale value pairs.

6

Get/Set

Sensitivity Units

ENGUNIT

Units of the denominator of the
Sensitivity Value.

See DeviceNet Specification Volume 1
Appendix K. Also see Parameter Object
instances 1 and 2 (

page 128

).

Valid values:
g = 1504

h

in/sec = 2B07

h

mil = 0800

h

psi = 1300

h

volt = 2D00

h

mm/s = 0900

h

μm = 2204

h

mbar = 1308

h

Pa = 1309

h

7

Get/Set

Fault High

REAL

The maximum expected DC Bias
voltage from the transducer in
volts.

Volts
A reading above this value causes a
transducer fault, which is indicated by the
Channel status indicator flashing red.