Transducer object (class id 328h), Class attributes, Instances – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 154: Instance attributes, Class attributes instances instance attributes, Refer to transducer object (class id 328h), Refer to transducer, Transducer object (class id 328

154
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Appendix B
CIP Objects
Transducer Object
(Class ID 328
H
)
The Transducer Object models a transducer.
Class Attributes
The Transducer Object provides no class attributes.
Instances
There are three instances of this object.
Instance Attributes
Table 79 - Band Measurement Object Instances
Instance
Descriptions
1
Vibration Channel 0
2
Vibration Channel 1
3
Tachometer Channel
Table 80 - Transducer Object Instance Attributes
Attr ID
Access Rule
Name Data
Type
Description
Semantics
3
Get
DC Bias
REAL
The measured average DC bias of
the transducer signal in volts.
Volts
4
Get
Status
BOOL
Indicates whether a transducer
fault exists (the measured DC Bias
is outside the range specified by
Fault High and Low).
0 = No fault
1 = A transducer fault exists
5
Get/Set
Sensitivity Value
REAL
Value of the sensitivity of the
transducer in millivolts per
Sensitivity Units.
See Valid Full Scale Selections for valid
Sensitivity and Full Scale value pairs.
6
Get/Set
Sensitivity Units
ENGUNIT
Units of the denominator of the
Sensitivity Value.
See DeviceNet Specification Volume 1
Appendix K. Also see Parameter Object
instances 1 and 2 (
Valid values:
g = 1504
h
in/sec = 2B07
h
mil = 0800
h
psi = 1300
h
volt = 2D00
h
mm/s = 0900
h
μm = 2204
h
mbar = 1308
h
Pa = 1309
h
7
Get/Set
Fault High
REAL
The maximum expected DC Bias
voltage from the transducer in
volts.
Volts
A reading above this value causes a
transducer fault, which is indicated by the
Channel status indicator flashing red.