Install the XM-124 Standard Dynamic Measurement Module

Chapter 1

Table 3

shows the on-board relay connections for the modules.

Figure 11 - Relay Connection Wiring, Normally Closed and Normally Opened

TIP

The Expansion Relay module can be connected to the module to provide
additional relays. Refer the XM-441 Expansion Relay Module User Manual
for wiring details.

IMPORTANT

The NO terminal descriptions correspond to a de-energized (unpowered)
relay.

When the relay is configured for non-failsafe operation, the relay is
normally de-energized.

When the relay is configured for failsafe operation, the relay is normally
energized, and the behavior of the NO terminals is inverted.

Table 3 - Relay Connections for the XM-124 Module

Configured for
Failsafe Operation

Wire Contacts

Relay Terminals

Nonalarm

Alarm

Closed Opened

COM

47

NO

48

Configured for
Non-Failsafe Operation

Wire Contacts

Relay Terminals
Contact

Nonalarm

Alarm

Opened

Closed

COM

47

NO

48

+

Power

Source

Contact

COM NO

M

+

Power

Source

Contact

COM NO

32377 M