Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 1

Install the XM-124 Standard Dynamic Measurement Module

European Hazardous Location Approval

ATTENTION: Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:

Touch a grounded object to discharge potential static.
Wear an approved grounding wrist strap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.

European Zone 2 Certification (The following applies when the product bears the Ex Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC
and has been found to comply with the Essential Health and Safety Requirements relating to the design and
construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to
this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-0, EN
60079-15, and EN 60079-11.

ATTENTION: This equipment is not resistant to sunlight or other sources of UV
radiation.

WARNING: The following warnings apply to installations of the XM-124.

This equipment must be installed in an enclosure providing at least IP54

protection when applied in Zone 2 environments.

This equipment shall be used within its specified ratings defined by Rockwell

Automation.

Provision shall be made to prevent the rated voltage from being exceeded by

transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.

Secure any external connections that mate to this equipment by using screws,

sliding latches, threaded connectors, or other means provided with this
product.

Do not disconnect equipment unless power has been removed or the area is

known to be nonhazardous.

This equipment shall be mounted in an ATEX certified enclosure with a

minimum ingress protection rating of at least IP54 (as defined in IEC60529)
and used in an environment of not more than Pollution Degree 2 (as defined in
IEC 60664-1) when applied in Zone 2 environments. The enclosure must use a
tool removable cover or door.

This equipment must be used only with ATEX certified Rockwell Automation

terminal bases.