Services, Relay object (class id 323h), Relay object (class id 323 – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 142

Advertising
background image

142

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Appendix B

CIP Objects

Services

(1)

Attributes can only be set while the device is in Program mode. See the description of the Device Mode Object for more information.

Relay Object (Class ID 323

H

)

The Relay Object models a relay (actual or virtual). A relay can be activated or
deactivated based on the status of one or more alarms.

7

Get

Time Constant

REAL

The detection time constant
associated with the output
smoothing filter (for the RMS and
DC meters) or the decay rate of the
peak meters.

This setting is based on the Low
Frequency Cutoff
(Channel object) and
Measurement (attribute 6).
If Measurement is set to 3 or 4, the
Overall Time Constant is 1.5 seconds.
If Measurement is set to 0, 1, or 2, the
table below shows the Time Constant.

8

Get

Damping Factor

REAL

The damping factor associated
with output smoothing filter for
the RMS and DC meters (not used
with peak meters).

1.0

9

Get/Set

Overall Filter

USINT

Overall filter type applied to the
input signal before the
measurement is performed.

0 = None
1 = Low Pass Filter
2…255 Reserved

10

Get/Set

Low Pass Corner
Frequency

UINT

The corner frequency of the low
pass filter.

100…20,000 Hz

Table 63 - Overall Measurement Object Instance Attributes

Attr ID

Access Rule

Name

Data Type

Description

Semantics

Low
Frequency
Cutoff

Overall
Time
Constant

0.2 Hz

0.8

1 Hz

0.16

5 Hz

0.045

10 Hz

0.045

40 Hz

0.045

Table 64 - Overall Measurement Object Services

Service Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Instance

Set_Attribute_Single

Sets a single attribute.

(1)