Chapter 2

Configure the XM-124 Standard Dynamic Measurement Module

measurements. Click Spectrum/Waveform to open the Spectrum/Waveform
options dialog box.

In this field

Values are

Comments

Sampling Mode

Choose the sampling mode:
Asynchronous
Synchronous with tach

The sampling mode determines whether the signal is
synchronized with the tachometer signal and has several
effects on the resulting measurements.

Synchronous sampling requires a tachometer signal.

Sampling Mode (continued)

Frequency Type

The frequency units (Hz or CPM).

Enter the FMAX in these units.

Asynchronous Sampling

Synchronous Sampling

The waveform measurement is
time-based

The waveform measurement is
position-based.

The spectrum measurement is
frequency-based.

The spectrum measurement is
order-based and the Number of
Lines must be evenly divisible
by Frequency Maximum.

The Frequency Maximum must
be specified in Hz.

Frequency Maximum must be
specified in orders.