Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 1

Install the XM-124 Standard Dynamic Measurement Module

connector cannot exceed 3 A. Refer to the specifications for the specific modules
for power requirements.

Figure 2 is an illustration of wiring modules using separate power connections.

Figure 2 - XM Modules with Separate Power Connections

Table 1 - Power Supply Requirements

ATTENTION: A separate power connection is necessary if the total current draw
of the interconnecting modules is greater than 3 A.

Any limited power
source that satisfies
the requirements
specified below

XM Power Supply Requirements

Protection

Listed Class 2 rated supply

Fused

(1)

ITE Listed SELF supply

Fused

(1)

ITE Listed PELV supply

Output Voltage

24V DC ± 10%

Output Power

100 W max (~4 A @ 24V DC)

Static Regulation

±2%

Dynamic Regulation

±3%

Ripple

<100 mV pp