Services – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 144

144
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Appendix B
CIP Objects
Services
(1)
Attributes can only be set while the device is in Program mode. See the description of the Device Mode Object for more information.
11
Get/Set
Alarm Identifier B
EPATH
Identifies the second alarm status
the relay monitors.
See Parameter Object instances 31…35.
12
Get/Set
Logic
USINT
Indicates the number of
associated alarms that must have
a status value specified by Alarm
Level to activate the relay.
0 = Ignore Alarm Identifier B and
activate the relay based on the status of
Alarm Identifier A.
1 = Activate the relay if the status of either
Alarm Identifier A or B matches any of
the statuses specified by Alarm Level.
2 = Activate the relay if the status of both
Alarm Identifier A and B match any of
the statuses specified by Alarm Level.
14
Get
Relay Installed
BOOL
Indicates whether an actual relay
is associated with this instance.
0 = Not installed
1 = Installed
15
Get/Set
Idle Hold
USINT
Hold relay state during
reconfiguration.
0 = Relay is deactivated while module is in
Program mode.
1 = Relay retains last state while in
Program mode.
Table 66 - Relay Object Instance Attributes
Attr ID
Access Rule
Name Data
Type
Description
Semantics
Table 67 - Relay Object Services
Service Code
Class/Instance Usage
Name
Description
05
h
Class/Instance
Reset
Resets latched relay.
0E
h
Class/Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Class/Instance
Set_Attribute_Single
Sets a single attribute.
(1)