Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Appendix B

CIP Objects

Services

(1)

Attributes can only be set while the device is in Program mode. See the description of the Device Mode Object for more information.

11

Get/Set

Alarm Identifier B

EPATH

Identifies the second alarm status
the relay monitors.

See Parameter Object instances 31…35.

See Table 48 on page 128

.

12

Get/Set

Logic

USINT

Indicates the number of
associated alarms that must have
a status value specified by Alarm
Level
to activate the relay.

0 = Ignore Alarm Identifier B and
activate the relay based on the status of
Alarm Identifier A.
1 = Activate the relay if the status of either
Alarm Identifier A or B matches any of
the statuses specified by Alarm Level.
2 = Activate the relay if the status of both
Alarm Identifier A and B match any of
the statuses specified by Alarm Level.

14

Get

Relay Installed

BOOL

Indicates whether an actual relay
is associated with this instance.

0 = Not installed
1 = Installed

15

Get/Set

Idle Hold

USINT

Hold relay state during
reconfiguration.

0 = Relay is deactivated while module is in
Program mode.
1 = Relay retains last state while in
Program mode.

Table 66 - Relay Object Instance Attributes

Attr ID

Access Rule

Name Data

Type

Description

Semantics

Table 67 - Relay Object Services

Service Code

Class/Instance Usage

Name

Description

05

h

Class/Instance

Reset

Resets latched relay.

0E

h

Class/Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Class/Instance

Set_Attribute_Single

Sets a single attribute.